beautypg.com

Rate alarm, Sensor offset, Rate alarm sensor offset – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 74

background image

74

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

Chapter 4

1756-IRT8I Combined Temperature-sensing Isolated Analog Module

Rate Alarm

The rate alarm triggers if the rate of change between input samples for each
channel

exceeds the specified trigger point for that channel. The actual rate of

change for the last sample is returned in the

Ch[x].RateOfChange input tag of

each channel.

To see where to set the Rate Alarm, see

page 131

.

Sensor Offset

The sensor offset value compensates for any known error on the sensor or
channel to which the sensor is connected. The value is set in signal units.

You set this value via a module output tags. That is, tag

O.Ch[x].SensorOffset.

Where x represents the module channel.

EXAMPLE

In normal scaling in Celsius, if you configure a channel’s rate alarm to
100.1 °C/s, the rate alarm triggers only if the difference between measured
input samples changes at a rate > 100.1 °C/s.

Consider the following conditions:

The module’s RPI is 100 ms, that is, new data is sampled every 100 ms.

At input sample #1, the channel measures 355 °C.

At input sample #2, (100 ms later) the channel measures 363 °C.

At this sample instance, the rate alarm is not triggered because the
rate of change is less than 100.1 °C/s.

The rate of change is 80 °C/s [(363 °C- 355 °C) / (100 ms)].

At input sample #3 (100 ms later) the channel measures 350.3 °C.

At this sample instance, the rate alarm is triggered because the rate
of change is greater than 100.1 °C.

The rate of change is 127 °C. [(350.3 °C - 363 °C) / (100 ms)].

At this sample instance, the absolute value of this result is > 100.1 °C,
so the rate alarm sets. Absolute value is used because rate alarm checks
for the magnitude of the rate of change being beyond the trigger point,
whether a positive or negative excursion.