Connect the ungrounded end of the cable – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 111

background image

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

111

Install ControlLogix Isolated Analog I/O Modules

Chapter 6

5.

Connect the drain wire to a chassis mounting tab.

Use any chassis mounting tab that is designated as a functional signal
ground. The functional earth ground symbol appears near the tab.

6.

When the drain wire is grounded, connect the insulated wires to the field-
side.

Connect the Ungrounded End of the Cable

1.

Cut the foil shield and drain wire back to the cable casing and apply shrink
wrap.

2.

Connect the insulated wires to the RTB.

Chassis Mounting Tab

Drain Wire with Ground Lug

4 m or 5 m (#10 or #12)
Star Washer

4 m or 5 m (#10 or #12) Star Washer Phillips Screw
and Star Washer (or SEM Screw)

20918-M

Functional Earth

Ground Symbol