beautypg.com

Connect wiring – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules  User Manual

Page 109

background image

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014

109

Install ControlLogix Isolated Analog I/O Modules

Chapter 6

Connect Wiring

Connect wiring to the module with an RTB or a Bulletin 1492 pre-wired Analog
Interface Module (AIFM). This section describes how to wire the module with
an RTB. If you are using an AIFM to connect wiring, see the documentation for
that product.

IMPORTANT

We recommend that you use Belden 8761 cable when wiring the RTB for the
following ControlLogix isolated analog modules:

1756-IF8I

1756-OF8I

1756-IRT8I on points that use the Thermocouple functionality

We recommend that you use Belden 9533 or 83503 cable with the 1756-IRT8I
module on points that use the RTD functionality.

WARNING: If you connect or disconnect wiring while the field-side power is on,
an electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before
proceeding.

ATTENTION: If multiple power sources are used, do not exceed the specified
isolation voltage.

ATTENTION: The ControlLogix system has been agency certified using only the
ControlLogix RTBs (catalog numbers 1756-TBCH, 1756-TBNH, 1756-TBSH and
1756-TBS6H). Any application that requires agency certification of the
ControlLogix system using other wiring termination methods may require
application specific approval by the certifying agency.