Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules User Manual
Page 183

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014
183
Isolated Analog I/O Module Tag Definitions
Appendix A
Ch[x].SensorType
SINT
Sensor type used on the channel. The Input Type
connected to the channel determine the sensor type
If an RTD input type is connected to
the channel:
• 0 = Ω
• 1 = 100Ω PT 385
• 2 = 200Ω PT 385
• 3 = 500Ω PT 385
• 4 = 1000Ω PT 385
• 5 = 100Ω PT 3916
• 6 = 200Ω PT 3916
• 7 = 500Ω PT 3916
• 8 = 1000Ω PT 3916
• 9 = 10Ω CU 427
• 10 = 120Ω NI 672
• 11 = 100Ω NI 618
• 12 = 120Ω NI 618
• 13 = 200Ω NI 618
• 14 = 500Ω NI 618
If a Thermocouple input type is
connected to the channel:
• 0 = mV
• 1 = B
• 2 = C
• 3 = E
• 4 = J
• 5 = K
• 6 = N
• 7 = R
• 8 = S
• 9 = T
• 10 = TXK/XK(L)
• 11 = D
Ch[x].NotchFilter
SINT
Notch Filter removes line noise for the channel.
There is a relationship between this setting and the RPI
setting. For more information on Notch Filter, see
• 0 = 10 Hz
• 1 = 50 Hz
• 2 = 60 Hz
• 3 = 100 Hz
• 5 = 1000 Hz
• 6 = 20 Hz
• 7 = 15 Hz
• 8 = 500 Hz
• 9 = 5000 Hz
• 10 = 5 Hz
Table 23 - 1756-IRT8I Module - Configuration Tags
Tag Name
Size
Definition
Valid Values