Calibration, Calibrated accuracy, Calibrated accuracy at 25 °c (77 °f) – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules User Manual
Page 38: Calibration calibrated accuracy
38
Rockwell Automation Publication 1756-UM540A-EN-P - May 2014
Chapter 2
ControlLogix Isolated Analog I/O Module Features
Calibration
The ControlLogix isolated analog modules are calibrated via the
following methods:
•
Factory calibration when the modules are built.
•
User-executed calibration as described in
ControlLogix Isolated Analog I/O Modules on page 137
User-executed calibration is optional.
• 1756-IRT8I module only
- Channels configured for Thermocouple
inputs perform a lead resistance self-calibration when the module power
is cycled.
Calibrated Accuracy
The Calibrated Accuracy specification represents the module’s accuracy when
its ambient temperature is the same as the temperature at which the module
was calibrated.
The following specifications are related to Calibrated Accuracy:
•
Calibrated Accuracy at 25 °C (77 °F)
•
Module Error over Full Temperature Range
Calibrated Accuracy at 25 °C (77 °F)
This specification matches the temperature at which the module was calibrated
in the factory during manufacturing.
The module’s accuracy when operating in 25 °C (77 °F) conditions = 0.05%.