Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules User Manual
Page 176
![background image](/manuals/579242/176/background.png)
176
Rockwell Automation Publication 1756-UM540A-EN-P - May 2014
Appendix A
Isolated Analog I/O Module Tag Definitions
Ch[x].RateAlarmLimit
REAL
Rate of change in Engineering Units/Second
If the absolute value of the change between samples
divided by the sample time exceeds this value, the
I.Ch[x].RateAlarm tag is sets.
Any positive value
0.0 = default (This value represents
no change between samples.)
Ch[x].LowSignal
REAL
Signal value that lets you scale signal units (V, mA) into
Engineering Units.
Corresponds to the C.Ch[x].LowEngineering tag. That is,
this tag’s value is scaled to the lowest Engineering Unit.
For more information on how Signal values correspond to
Engineering values, see
Any value that is less than the
C.Ch[x].HighSignal tag value.
• Current input type: 4.0 mA =
default
• Voltage input type: -10.0V=
default
Ch[x].HighSignal
REAL
Signal scaling value that lets you scale signal units (V, mA)
into Engineering Units.
Corresponds to the C.Ch[x].HighEngineering tag. That is,
this tag’s value is scaled to the highest Engineering Unit.
For more information on how Signal values correspond to
Engineering values, see
Any value that is greater than the
C.Ch[x].LowSignal tag value
• Current input type: 20.0 mA =
default
• Voltage input type: 10.0V=
default
Ch[x].LowEngineering
REAL
Low engineering scaling point
Corresponds to the C.Ch[x].LowSignal tag value.
For more information on how Signal values correspond to
Engineering values, see
0.0 = default
(In voltage applications, default =
C.Ch[x].LowSignal tag value)
Ch[x].HighEngineering
REAL
High engineering scaling point
Corresponds to the C.Ch[x].HighSignal tag value.
For more information on how Signal values correspond to
Engineering values, see
100.0 = default
(In voltage applications, default =
C.Ch[x].HighSignal tag value)
Ch[x].LLAlarmLimit
REAL
Low Low Process Alarm limit
Triggers the I.Ch[x].LLAlarm tag when the I.Ch[x].Data tag
value is less than this tag’s value.
0.0 = default
Ch[x].LAlarmLimit
REAL
Low Process Alarm limit
Triggers the I.Ch[x].LAlarm tag when the I.Ch[x].Data tag
value is less than this tag’s value
0.0 = default
Ch[x].HAlarmLimit
REAL
High Process Alarm Limit
Triggers the I.Ch[x].HAlarm tag when the I.Ch[x].Data tag
value is greater than this tag’s value.
100.0 = default
Ch[x].HHAlarmLimit
REAL
High High Process Alarm Limit
Triggers the I.Ch[x].HHAlarm tag when the I.Ch[x].Data
tag value is greater than this tag’s value.
100.0 = default
Ch[x].AlarmDeadband
REAL
Deadband that keeps Process Alarms triggered as long as
the I.Ch[x].Data tag value remains within the deadband of
the Process Alarm’s value
Any non-negative value
0.0 = default
Table 20 - 1756-IF8I Module - Configuration Tags
Tag Name
Size
Definition
Valid Values