Calibrate the ControlLogix Isolated Analog I/O Modules

Chapter 8

5.

On the Calibration tab, click Start Calibration.

6.

When the warning appears, click OK.

7.

Select the channels to be calibrated and click Next.

The Attach Low Reference Voltage Signals dialog box appears, as shown
below. It indicates the channels are calibrated for a low reference and the
range of the calibration.