Rockwell Automation Publication 1756-UM540A-EN-P - May 2014
Chapter 2
ControlLogix Isolated Analog I/O Module Features
To see where to configure Electronic Keying, see
.
EXAMPLE
In the following scenario, Disable keying lets I/O
communication occur:
The module configuration is for a 1756-IA16 digital input module. The
physical module is a 1756-IB16 digital input module. In this case,
communication is allowed because the two digital modules share common
data formats.
IMPORTANT
Changing electronic keying selections online can cause the I/O
communication connection to the module to be disrupted and can result in
a loss of data.
Module Configuration
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IA16
Major Revision = 2
Minor Revision = 1
Physical Module
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16
Major Revision = 3
Minor Revision = 2
Communication is allowed