Fault and status reporting – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules User Manual
Page 102
102
Rockwell Automation Publication 1756-UM540A-EN-P - May 2014
Chapter 5
1756-OF8I Isolated Analog Output Module
Fault and Status Reporting
The 1756-OF8I module multicasts fault and status data with channel data to the
owner and listening controllers. The data is returned via module tags that you can
monitor in your Logix Designer application.
With some exceptions, as noted in the following table, the 1756-OF8I module
provides the fault and data status in a channel-centric format.
The following table lists the 1756-OF8I module’s fault and status tags available
in the Logix Designer application.
Table 15 - 1756-OF8I Module - Fault and Status Data Tags
Data Type
Tag Name
Triggering Event That Sets Tag
Fault
Fault
(1)
The owner-controller loses its connection to the module.
Ch[x].Fault
The channel data quality is bad.
Status
CIPSyncValid
Indicates whether the module has synchronized to a valid CIP Sync time master on the backplane.
CIPSyncTimeout
Indicates whether a valid time master on the backplane has timed out.
CIPSyncOffsetJump
Indicates a significant jump, that is, 1 ms or greater, in the CST and CIP Sync times sent from the Timemaster to the
module. (The Timemaster sends the CST and CIP Sync times to the module every second.)
When a significant jump occurs, this tag value becomes 1 but changes to 0 a second later unless another jump
occurred.
Ch[x].Uncertain
The channel data can be imperfect.
Ch[x].LowClampAlarm
The following events occur:
• Clamping is enabled on this channel.
• One of the following:
– The channel data requested, indicated in the O.Ch[x].Data tag, is currently less than the configured LowLimit.
– Latching is enabled and the O:Ch[x].Data tag was less than the configured LowLimit at some points and the
alarm has not been unlatched.
Ch[x].HighClampAlarm
The following events occur:
• Clamping is enabled on this channel.
• One of the following:
– The channel data requested, indicated in the O.Ch[x].Data tag, is currently greater than the configured
HighLimit.
– Latching is enabled and the O:Ch[x].Data tag was greater than the configured HighLimit at some points and
the alarm has not been unlatched.
Ch[x].RampAlarm
The channel is currently limited to changing the output at the Maximum Ramp rate or once was and is now latched.
Ch[x].NotANumber
The most recently-received data value was not a number.
Ch[x].InHold
The channel is currently holding until the received channel data is within 0.1% of the current channel data value.
Ch[x].CalibrationFault
The last attempted Calibration for this channel failed.
Ch[x].Calibrating
The channel is currently being calibrated.
Ch[x].CalGoodLowRef
A valid Low Reference signal has been sampled on this channel.
Ch[x].CalBadLowRef
An invalid Low Reference signal has been sampled on this channel.
Ch[x].CalGoodHighRef
An valid High Reference signal has been sampled on this channel.
Ch[x].CalBadHighRef
An invalid High Reference signal has been sampled on this channel.
Ch[x].CalSuccessful
Calibration on this channel is complete and the Calibrating state has been exited.
Ch[x].Data
The channel data in scaled Engineering Units. This data is the Output Data Echo data returned from the D/A convertor.
Timestamp
A 64-bit Timestamp indicating when any one of the output channels was last updated with new output data in terms
of CIPSync time.
RollingTimestamp
16 bit timestamp that ‘rolls’ from 0…32,767 ms. Compatible with existing PID instruction to automatically calculate
sample deltas.
(1) This tag provides module-wide data and affects all channels simultaneously.