Chapter 4
1756-IRT8I Combined Temperature-sensing Isolated Analog Module
Fault and Status Reporting
The 1756-IRT8I module multicasts fault and status data with channel data to the
owner and listening controllers. The data is returned via module tags that you can
monitor in your Logix Designer application.
With some exceptions, as noted in the following table, the 1756-IRT8I module
provides the fault and data status in a channel-centric format.
The following table lists the 1756-IRT8I module’s fault and status tags available
in the Logix Designer application.
Table 13 - 1756-IRT8I Module - Fault and Status Data Tags
Data Type
Tag Name
Triggering Event That Sets Tag
Fault
Fault
(1)
The owner-controller loses its connection to the module.
CJ[x].Underrange
The cold junction for the channel is below 0 °C
CJ[x].Overrange
The cold junction for the channel is above 86 °C
Ch[x].Fault
The channel data quality is bad.
Ch[x].Underrange
The channel data is beneath the absolute minimum for this channel.
Ch[x].Overrange
The channel data is above the absolute maximum for this channel.
Status
CIPSyncValid
Indicates whether the module has synchronized to a valid CIP Sync time master on the backplane.
CIPSyncTimeout
Indicates whether a valid time master on the backplane has timed out.
CIPSyncOffsetJump
Indicates a significant jump, that is, 1 ms or greater, in the CST and CIP Sync times sent from the Timemaster to the
module. (The Timemaster sends the CST and CIP Sync times to the module every second.)
When a significant jump occurs, this tag value becomes 1 but changes to 0 a second later unless another jump
occurred.
Ch[x].Uncertain
The channel data can be imperfect.
Ch[x].LLAlarm
The I.Ch[x].Data tag value is less than the C.Ch[x].LLAlarmLimit tag value, the O.Ch[x].LLAlarmEn tag is set and alarms
are enabled for the channel.
Ch[x].LAlarm
The I.Ch[x].Data tag value is less than the C.Ch[x].LAlarmLimit tag value, the O.Ch[x].LAlarmEn tag is set and alarms
are enabled for the channel.
Ch[x].HAlarm
The I.Ch[x].Data tag value is greater than the C.Ch[x].HAlarmLimit tag value, the O.Ch[x].HAlarmEn tag is set and
alarms are enabled for the channel.
Ch[x].HHAlarm
The I.Ch[x].Data tag value is greater than the C.Ch[x].HHAlarmLimit tag value, the O.Ch[x].HHAlarmEn tag is set and
alarms are enabled for the channel.
Ch[x].RateAlarm
The absolute change between consecutive channel samples exceeds the C.Ch[x].RateAlarmLimit tag value.
This alarm only applies to enabled Process alarms.
Ch[x].CalibrationFault
The last attempted Calibration for this channel failed.
Ch[x].Calibrating
The channel is currently being calibrated.
Ch[x].CalGoodLowRef
A valid Low Reference signal has been sampled on this channel.
Ch[x].CalBadLowRef
An invalid Low Reference signal has been sampled on this channel.
Ch[x].CalGoodHighRef
An valid High Reference signal has been sampled on this channel.
Ch[x].CalBadHighRef
An invalid High Reference signal has been sampled on this channel.
Ch[x].CalSuccessful
Calibration on this channel is complete and the Calibrating state has been exited.
Ch[x].RateOfChange
The change in channel data since last sample in Engineering Units/Second.
Ch[x].Data
The channel data in scaled Engineering Units.
Timestamp
A 64-bit Timestamp indicating when all 8 channels were last sampled in terms of CIPSync time.
RollingTimestamp
16 bit timestamp that ‘rolls’ from 0…32,767 ms. Compatible with existing PID instruction to automatically calculate
sample deltas.
(1) This tag provides module-wide data and affects all channels simultaneously.