Rockwell Automation 20D PowerFlex 700S Phase II Drive Frames 1...6 Installation Instructions User Manual
Page 51

Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
51
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Table 21 - 810 Volt DC Input Frames 1…6 Drive Protection Devices
Table 22 - 932Volt DC Input Frames 5 & 6 Drive Protection Devices
20DJ180
6
150
–
198
400
HSJ400
–
125
171.2
400
HSJ400
20DJ248
6
200
–
272
400
HSJ400
–
150
198
400
HSJ400
(1) Also applies to “R” voltage class. s must be applied in the (+) leg and (-) leg of the DC Common Bus.
(2) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.
Drive Cat. No.
Frame HP Rating
DC Input Ratings
Fuse
Non-Time Delay
(1)
(1) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.
ND
HD
Amps
20DE1P7
1
1
0.75 1.5
3
JKS-3
20DE2P7
1
2
1.5
2.4
6
JKS-6
20DE3P9
1
3
2
3.5
6
JKS-6
20DE6P1
1
5
3
6.2
10
JKS-10
20DE9P0
1
7.5
5
9.1
15
HSJ15
20DE011
1
10
7.5
11.5
20
HSJ20
20DE017
1
15
10
18
30
HSJ30
20DE022
2
20
15
23.6
40
HSJ40
20DE027
2
25
20
29
50
HSJ50
20DE032
3
30
25
34.3
60
HSJ60
20DE041
3
40
30
43.9
70
HSJ70
20DE052
3
50
40
55.7
90
HSJ90
20DE062
4
60
50
68.0
125
HSJ125
20DT099
5
100
–
108.6
150
HSJ150
–
75
84.5
150
HSJ150
20DT144
6
150
–
158
200
HSJ200
–
125
137.1
200
HSJ200
Drive Cat. No.
Frame kW Rating
DC Input Ratings
Fuse
Non-Time Delay
(1)
(1) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.
ND
HD
Amps
20DW098
5
90
–
92.3
160
HSJ160
–
75
92.3
160
HSJ160
20DW142
6
132
–
162.2
250
HSJ250
–
110
134.9
250
HSJ250
Drive Cat. No.
Frame
HP Rating
DC Input Ratings
Fuse
Non-Time Delay
(2)
ND
HD
Amps