beautypg.com

Rfi filter ground – Rockwell Automation 20D PowerFlex 700S Phase II Drive Frames 1...6 Installation Instructions User Manual

Page 26

background image

26

Rockwell Automation Publication 20D-IN024C-EN-P - July 2013

PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control

Unbalanced, Ungrounded or Resistive Grounded Distribution
Systems

If phase to ground voltage will exceed 125% of normal or the supply system is
ungrounded, refer to Wiring and Grounding Guidelines for Pulse Width
Modulated (PWM) AC Drives, publication

DRIVES-IN001

, for more

information.

RFI Filter Ground

Using an optional RFI filter may result in relatively high ground leakage currents.
Therefore, the filter must only be used in installations with grounded AC supply
systems and be permanently installed and solidly grounded (bonded) to the
building power distribution ground. Be sure that the incoming supply neutral is
solidly connected (bonded) to the same building power distribution ground.
Grounding must not rely on flexible cables and should not include any form of
plug or socket that would permit inadvertent disconnection. Some local codes
may require redundant ground connections. The integrity of all connections
should be periodically checked. Refer to the instructions supplied with the filter.

ATTENTION: PowerFlex 700S drives contain protective MOVs and common
mode capacitors that are referenced to ground. These devices must be
configured according to the recommendations in

Table 10

on page

27

.

This manual is related to the following products: