Rockwell Automation 20D PowerFlex 700S Phase II Drive Frames 1...6 Installation Instructions User Manual
Page 48

48
Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Table 16 - 600 Volt AC Input Frames 1…6 Drive Protection Devices
20DD125
5
100
–
117
97.6
150
250
150
500
375
150
–
–
–
–
–
75
90.1
74.9
125
200
125
350
350
125
–
–
–
–
20DD156
6
125
–
146.5
121.7
200
350
200
600
450
250
–
–
–
–
–
100
131
97.6
175
250
175
500
375
250
–
–
–
–
20DD180
6
150
–
169
140.5
225
400
225
600
500
250
–
–
–
–
–
125
147
121.7
200
350
200
600
450
250
–
–
–
–
20DD248
6
200
232.8
188
300
550
300
700
700
400
–
–
–
–
150
169
140.5
225
400
225
600
500
250
–
–
–
–
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(6)
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(8)
The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See
(9)
When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger
enclosure.
Drive Cat.
No.
Fr
am
e
HP Rating
Input Ratings
Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
140M Motor Starter with Adjustable Current Range
(6)(7)
ND
HD
Amps
kVA
Min
(1)
Max
(2)
Min
(3)
Max
(4)
Max
(4)
Max
(6)
Available Cat. No.s
(8)
Minimum Enclosure
Volume (in.
3
)
(9)
Drive
Cat. No.
Fr
am
e
HP Rating
Input Ratings
Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
140M Motor Starter with Adjustable Current Range
(6)(7)
ND
HD
Amps
kVA
Min
(1)
Max
(2)
Min
(3)
Max
(4)
Max
(4)
Max
(6)
Available Cat. No.s
(8)
Minimum Enclosure
Volume (in.
3
)
(9)
20DE1P7
1
1
0.75
1.3
1.4
2
4
2
6
15
3
M-C2E-B16
–
–
7269
20DE2P7
1
2
1.5
2.1
2.1
3
6
3
10
15
3
M-C2E-B25
–
–
7269
20DE3P9
1
3
2
3.0
3.1
6
9
6
15
15
7
M-C2E-B40
M-D8E-B40
–
7269
20DE6P1
1
5
3
5.3
5.5
9
12
9
20
20
15
–
M-D8E-B63
–
7269
20DE9P0
1
7.5
5
7.8
8.1
10
20
10
35
30
15
–
M-D8E-C10
M-F8E-C10
7269
20DE011
1
10
7.5
9.9
10.2
15
25
15
40
40
15
–
M-D8E-C10
M-F8E-C10
7269
20DE017
1
15
10
15.4
16.0
20
40
20
60
50
20
–
M-D8E-C16
M-F8E-C16
7269
20DE022
2
20
15
20.2
21.0
30
50
30
80
80
30
–
–
M-F8E-C25
7269
20DE027
2
25
20
24.8
25.7
35
60
35
100
100
50
–
–
M-F8E-C25
7269
20DE032
3
30
25
29.4
30.5
40
70
40
125
125
50
–
–
M-F8E-C32
13630
20DE041
3
40
30
37.6
39.1
50
90
50
150
150
100
–
–
–
–
20DE052
3
50
40
47.7
49.6
60
110
60
200
200
100
–
–
–
–
20DE062
4
60
50
58.2
60.5
80
125
80
225
225
100
–
–
–
–
20DE077
5
75
–
72.3
75.1
90
150
90
300
300
100
–
–
–
–
–
60
58.2
60.5
90
125
90
250
250
100
–
–
–
–
20DE099
5
100
–
92.9
96.6
125
200
125
375
375
150
–
–
–
–
–
75
72.3
75.1
100
175
100
300
300
100
–
–
–
–
20DE125
6
125
–
117
121.6
150
250
150
375
375
250
–
–
–
–
–
100
93
96.6
125
200
125
375
375
150
–
–
–
–
20DE144
6
150
–
135
140.5
175
300
175
400
400
250
–
–
–
–
–
125
117
121.6
150
275
150
375
375
250
–
–
–
–
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(6)
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(8)
The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See
(9)
When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger
enclosure.