Cable entry plate removal, Power wiring access panel removal – Rockwell Automation 20D PowerFlex 700S Phase II Drive Frames 1...6 Installation Instructions User Manual
Page 38

38
Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Cable Entry Plate Removal
If additional wiring access is needed, the cable entry plate on frame 1…3 drives
can be removed. Loosen the screws securing the plate to the chassis and slide the
plate down and off the drive.
Power Wiring Access Panel Removal
IMPORTANT
Removing the cable entry plate on frame 1…3 limits the maximum
surrounding air temperature to 40 °C (104 °F).
ATTENTION: Removing the access panel/cover exposes dangerous voltages on
the terminals and negates the enclosure type rating. Replace the access panel/
cover when service is complete. Failure to comply may result in personal injury
or equipment damage.
Frame
Removal Procedure (Replace when wiring is complete)
1, 2 & 6
The access panel is part of the front cover, see
3
Open front cover and gently tap/slide the access panel down and out.
4
Loosen the 4 screws and remove the access panel.
5
on page
) and gently tap/slide the access panel up and out.
SHLD
SHLD
PE
(Frame 3 Shown)