beautypg.com

Figure 12, Fan va rating (dc input drives only), Frame 5 and 6 transformer tap access – Rockwell Automation 20D PowerFlex 700S Phase II Drive Frames 1...6 Installation Instructions User Manual

Page 35

background image

Rockwell Automation Publication 20D-IN024C-EN-P - July 2013

35

PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control

Fan VA Rating (DC Input Drives Only)

Figure 12 - Phase Selection Jumper and Fan Transformer Locations (Frame 5 shown)

Frame 5 and 6 Transformer Tap Access

The transformer is located behind the power terminal block in the area shown in

Figure 12

. Access is gained by releasing the terminal block from the rail. To

release terminal block and change tap:

1. Locate the small metal tab at the bottom of the end block.

2. Press the tab in and pull the top of the block out. Repeat for next block if

desired.

3. Select appropriate transformer tap.

4. Replace block(s) in reverse order.

Frame Fan Voltage (120V or 240V)
5

100 VA

6

138 VA

WIRE RANGE: 14-1/0 AWG (2.5-35 MM

2

)

TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM

2

)

TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM

2

)

TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

480 Volt Tap

600 Volt Tap

690 Volt Tap

400 Volt Tap

400 Volt or 600 Volt Tap

480V or 690 Volt Tap

LINE
TYPE

SPARE 1

SPARE 2

3-PH 1-PH

Line Type Jumper

Fan Voltage Selection

(Frame 5 shown)

Older drives

Newer drives

This manual is related to the following products: