PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Fan VA Rating (DC Input Drives Only)
Figure 12 - Phase Selection Jumper and Fan Transformer Locations (Frame 5 shown)
Frame 5 and 6 Transformer Tap Access
The transformer is located behind the power terminal block in the area shown in
. Access is gained by releasing the terminal block from the rail. To
release terminal block and change tap:
1. Locate the small metal tab at the bottom of the end block.
2. Press the tab in and pull the top of the block out. Repeat for next block if
desired.
3. Select appropriate transformer tap.
4. Replace block(s) in reverse order.
Frame Fan Voltage (120V or 240V)
5
100 VA
6
138 VA
WIRE RANGE: 14-1/0 AWG (2.5-35 MM
2
)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY
POWER TERMINAL RATINGS
WIRE RANGE: 6-1/0 AWG (16-35 MM
2
)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
GROUND TERMINAL RATINGS (PE)
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM
2
)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
17
21
INPUT AC
OUTPUT
Optional
Communications
Module
9
480 Volt Tap
600 Volt Tap
690 Volt Tap
400 Volt Tap
400 Volt or 600 Volt Tap
480V or 690 Volt Tap
LINE
TYPE
SPARE 1
SPARE 2
3-PH 1-PH
Line Type Jumper
Fan Voltage Selection
(Frame 5 shown)
Older drives
Newer drives