Table 17 - 690 Volt AC Input Frames 5 & 6 Drive Protection Devices

Table 18 - 325 Volt DC Input Frames 1…6 Drive Protection Devices

Drive
Cat. No.

Fr

am

e

kW Rating

Input Ratings

Dual Element Time Delay
Fuse

Non-Time Delay Fuse

Circuit Breaker

(3)

Motor Circuit Protector

(5)

ND

HD

Amps

kVA

Min

(1)

Max

(2)

Min

(2)

Max

(3)

Max

(4)

Max

(5)

20DF052

5

45

46.9

59.5

60

110

60

175

175

37.5

40.1

48.0

50

90

50

150

150

20DF060

5

55

57.7

68.9

80

125

80

225

225

45

46.9

59.5

60

110

60

175

175

20DF082

5

75

79.0

94.4

100

200

100

375

375

55

57.7

68.9

80

125

80

225

225

20DF098

5

90

94.7

113

125

200

125

375

375

75

79.0

94.4

100

200

100

375

375

20DF119

6

110

115

138

150

250

150

400

90

92.9

113

125

200

125

375

20DF142

6

132

139

165.9

175

300

175

450

110

115

137

150

250

150

400

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(4)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(5)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

Drive Cat. No.

Frame

HP Rating

DC Input Ratings

Fuse

Non-Time Delay

(3)

(3) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).

Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Ferraz Shawmut Type HSJ, all sizes. For any other devices, please contact the factory.

ND

HD

Amps

20DB015

1

5

3

16

30

HSJ30

20DB022

1

7.5

5

23.3

45

HSJ45

20DB028

2

10

7.5

30

60

HSJ60

20DB042

3

15

10

45

90

HSJ90

20DB052

3

20

15

55

100

HSJ100

20DB070

4

25

20

75.3

150

HSJ150

20DB080

4

30

25

85.8

175

HSJ175

20DN104

(1)

(1) Catalog number corresponds to output amps for these drives. Drive must be programmed to lower voltage to obtain higher currents

shown at right.

5

40

30

114.1

225

HSJ225

20DN130

(1)

5

50

40

142.6

250

HSJ250

20DN154

(1)

6

60

50

169

300

HSJ300

20DN192

(1)

6

75

60

210.6

400

HSJ400

20DN260

(1)(2)

(2) Catalog number corresponds to drives with precharge only.

6

100

75

272.1

400

HSJ400