PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Table 17 - 690 Volt AC Input Frames 5 & 6 Drive Protection Devices
Table 18 - 325 Volt DC Input Frames 1…6 Drive Protection Devices
Drive
Cat. No.
Fr
am
e
kW Rating
Input Ratings
Dual Element Time Delay
Fuse
Non-Time Delay Fuse
Circuit Breaker
(3)
Motor Circuit Protector
(5)
ND
HD
Amps
kVA
Min
(1)
Max
(2)
Min
(2)
Max
(3)
Max
(4)
Max
(5)
20DF052
5
45
–
46.9
59.5
60
110
60
175
175
–
–
37.5
40.1
48.0
50
90
50
150
150
–
20DF060
5
55
–
57.7
68.9
80
125
80
225
225
–
–
45
46.9
59.5
60
110
60
175
175
–
20DF082
5
75
–
79.0
94.4
100
200
100
375
375
–
–
55
57.7
68.9
80
125
80
225
225
–
20DF098
5
90
–
94.7
113
125
200
125
375
375
–
–
75
79.0
94.4
100
200
100
375
375
–
20DF119
6
110
–
115
138
150
250
150
400
–
–
–
90
92.9
113
125
200
125
375
–
–
20DF142
6
132
–
139
165.9
175
300
175
450
–
–
–
110
115
137
150
250
150
400
–
–
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
Drive Cat. No.
Frame
HP Rating
DC Input Ratings
Fuse
Non-Time Delay
(3)
(3) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Ferraz Shawmut Type HSJ, all sizes. For any other devices, please contact the factory.
ND
HD
Amps
20DB015
1
5
3
16
30
HSJ30
20DB022
1
7.5
5
23.3
45
HSJ45
20DB028
2
10
7.5
30
60
HSJ60
20DB042
3
15
10
45
90
HSJ90
20DB052
3
20
15
55
100
HSJ100
20DB070
4
25
20
75.3
150
HSJ150
20DB080
4
30
25
85.8
175
HSJ175
20DN104
(1)
(1) Catalog number corresponds to output amps for these drives. Drive must be programmed to lower voltage to obtain higher currents
shown at right.
5
40
30
114.1
225
HSJ225
20DN130
(1)
5
50
40
142.6
250
HSJ250
20DN154
(1)
6
60
50
169
300
HSJ300
20DN192
(1)
6
75
60
210.6
400
HSJ400
20DN260
(1)(2)
(2) Catalog number corresponds to drives with precharge only.
6
100
75
272.1
400
HSJ400