Reader setup – SDC E5 Series Access Control System User Manual
Page 3

In a networked system, each reader must be assigned a unique Terminal Address Number .
The factory default terminal address number of “01”. Follow the procedure below to change the
readers Terminal Address Number at each reader. Mark the reader’s name on the reference
chart (Page iv). You will enter the location later in the reader parameter section of the sofware on
the PC.
Reader Setup
Enter Programming
Mode
Press and Hold the ‘#” for
3 seconds
0. CHECK VERSION
1. SETUP
FUNCTION
PROCEDURE
DISPLAY WILL SHOW
Enter Setup
Enter “1”
PASSWORD:
Enter Password
Enter “1111” + “#”
1. ENROL 2. PASSWD
3. TIMER 4. SYSTEM
Select System Menu
Enter “4”
1. ALARM 2. MODE
3. COMM 4. OTHER
Select Communications
Menu
Enter “3”
1. ADDRESS 2. BAUD
3. FORMAT 4. RECO
Select Terminal Address
Menu
Enter “1”
1. ADDRESS : 01
. NEW:_
Enter New Terminal
Number
Enter “Terminal No.” + “#”
(for example “02”)
1. ADDRESS : 02
. NEW:_
Exit Programming Mode
Enter “#”
READY FOR CARD
####/## ##:##
PC
Front Door
Rear Door
Side Door
Terminal
Address
01
Terminal
Address
02
Terminal
Address
03
RS485/RS232 OR
RS485/USB
Converter
CONNECTING
E5P READERS
TO CREATE A
NETWORKED
SYSTEM
RS485 from readers
TR-
TR+
Each reader must have a separate Terminal Address
GND (-)
D-
D+
SG
P:\Installation Instructions\Access Controls\Inst-E5\INST-E5.vsd Rev C 03-13 Page: 2