7 executing a reset node, Executing a reset node, Configuring system bus (can) – Lenze ECSCExxx Power supply module User Manual
Page 94

Configuring system bus (CAN)
Executing a reset node
l
94
EDBCSXE040 EN 7.0
8.7
Executing a reset node
The following changes will only be valid after a reset node:
ƒ
Changes of the CAN node addresses and baud rates (
^
ƒ
Changes of the addresses of process data objects (COB−IDs)
– General addressing (
^
– Individual addressing (
^
ƒ
Change of the master/slave boot up configuration (
^
A reset node can be made by:
ƒ
Switching on again the low−voltage supply
ƒ
Reset node via the bus system (by the network management (NMT))
ƒ
Reset node with C0358 = 1 by means of keypad XT
– If the reset node is executed via GDC, the communication will be interrupted as a
matter of principle. Thus, it is required to log in again manually or to research the
devices connected to the bus.
Parameter
C0358
Designation
CAN reset node
Data type: INTEGER_32
Index: 24217
dec
= 5E99
hex
Make a reset node for the CAN bus node.
^ 94
Selection list
(Lenze setting printed in bold)
Information
0 No function
1 CAN reset