2 diagnostics pdo (c0390/1 ), Diagnostics pdo (c0390/1 ), Configuring system bus (can) – Lenze ECSCExxx Power supply module User Manual
Page 98

Configuring system bus (CAN)
Diagnostics codes
Diagnostics PDO (C0390/1 ... 8)
l
98
EDBCSXE040 EN 7.0
8.10.2
Diagnostics PDO (C0390/1 ... 8)
Parameter
C0390
Name
Configuration diagnostics PDO via CAN
Data type: INTEGER_32
Index: 24185
dec
= 5E79
hex
Via C0390/1 ... 8 a diagnostics PDO (8 bytes) can be parameterised, which can be sent via CAN2_OUT.
l
The 8 bytes can be assigned with variables for advanced diagnostics of the mains conditions and the internal
state machine (mapping).
l
In C0391 the assignment in percent (0 ... 100 %) of the 8 bytes of the PDO is shown.
Conditions for sending the diagnostics PDO:
The CAN bus is "Operational" and the cycle time for CAN2_OUT is > 0 ms (C0356/2).
Possible settings
C390/x = 0 Not assigned [0 bytes]
C390/x = 1 Voltage V
L1L2
[2 bytes]
C390/x = 2 Voltage V
L2L3
[2 bytes]
C390/x = 3 Counter of the zero crossings per second (frequency measurement of V
L1L2
) [2 bytes]
C390/x = 4 Mains synchronisation n−times outside the limits (evaluation of V
sd
and V
sq
) [1 byte]
C390/x = 5 Internal status bits [1 byte]
C390/x = 6 Transformed voltage component V
sd
[2 bytes]
C390/x = 7 Transformed voltage component V
sq
[2 bytes]
C390/x = 8 Internal error bits [2 bytes]
Subcodes
Information
C0390/1
Depending on the byte size of the variables selected, it
may happen that the variables in the last subcodes do
not become effective anymore.
^ 113
...
C0390/8