Appendix, Codes – Lenze ECSCExxx Power supply module User Manual
Page 138

Appendix
Codes
l
138
EDBCSXE040 EN 7.0
Parameter
C0356
Name
CAN time settings
Data type: INTEGER_32
Index: 24219
dec
= 5E9B
hex
Setting of the ...
l
Boot−up time
l
Cycle time
l
Activation delay
^ 90
Setting range
(min. value | unit | max. value)
0
ms
65000
Subcodes
Lenze setting
Information
C0356/1
3000 ms
CAN boot−up time
l
Delay time after mains connection for the
initialisation by the master.
l
Only valid if C0352 = 1 (master).
C0356/2
0 ms
Cycle time for CAN2_OUT
l
Diagnostics PDO C0390 (
^ 98)
C0356/3
0 ms
Cycle time for CAN3_OUT
l
Factor to task time for process data telegram
transmission.
l
0 ms = event−controlled data transmission (the
output data will only be transmitted if a value
changes in the output object)
C0356/4
20 ms
Delay time for initial transmission of the process data
object CAN3_OUT after the CAN bus changes to
"Operational"
Parameter
C0357
Designation
CAN_IN monitoring times (CE1 ... CE3)
Data type: INTEGER_32
Index: 24218
dec
= 5E9A
hex
Monitoring times for process data input objects
l
If no telegram arrives within the time set, CE1 ... CE3−TRIP is enabled.
l
Setting "0 ms" = monitoring is switched off
^ 108
Setting range
(min. value | unit | max. value)
0
ms
65000
Subcodes
Lenze setting
Information
C0356/1
0 ms
CAN1_IN monitoring time CE1
(cyclic operation (sync−controlled))
C0356/2
0 ms
CAN2_IN monitoring time CE2
(reserved)
C0356/3
0 ms
CAN3_IN monitoring time CE3
(event−controlled/cyclic operation without sync)
Parameter
C0358
Designation
CAN reset node
Data type: INTEGER_32
Index: 24217
dec
= 5E99
hex
Make a reset node for the CAN bus node.
^ 94
Selection list
(Lenze setting printed in bold)
Information
0 No function
1 CAN reset