1 basic settings with gdc, Basic settings with gdc, Commissioning – Lenze ECSCExxx Power supply module User Manual
Page 62

Commissioning
Commissioning steps (overview)
Basic settings with GDC
l
62
EDBCSXE040 EN 7.0
6.1.1
Basic settings with GDC
)
Note!
Follow the commissioning steps in the given order!
Setting
Brief description
Detailed
information
Conditions
l
Mains is switched off. (Green LED is dark, red LED is
blinking)
l
Power supply module is inhibited.
– Control bit 1 (STE_RESET) = 0
– Power supply enable input X6/DI1 = LOW
l
For operation in an EtherCAT network:
– Plug EtherCAT communication module (EMF2192IB)
onto AIF interface (X1).
1.
Switch on low−voltage supply.
2.
XT keypad or
Connect PC/laptop (with
installed GDC parameter
setting program) to the
power supply module.
Parameter setting with XT keypad
l
Plug the XT keypad into the AIF interface (X1).
l
Not possible for operation in an EtherCAT network, since
the AIF interface (X1) is already assigned by the EtherCAT
module (see "Preconditions" above).
^ 76
Parameter setting with GDC
l
Connect PC/laptop to system bus interface (X4) with PC
system bus adapter EMF2173IB/EMF2177IB.
l
Start GDC and select the device to be set.
^ 74
3.
Set mains voltage.
Setting via C0173
l
Setting of the connected ECS axis modules:
– C0173: Set DC bus thresholds according to the mains
voltage used.
– Set C0175 = 3 (charging current limitation is not active)
^ 67
4.
Set function of the brake
resistor.
Setting via C0127
(Brake chopper and/or fast discharge function (short−circuit
braking))
^ 68
5.
Only for operation with
external brake resistor:
Deactivate monitoring of the
internal brake resistor.
C0579 = 3 (internal brake resistor deactivated)
^ 71
6.
Configure power supply
enable input.
l
DC bus is charged if X6/DI1 = HIGH
l
Set the response of the power supply module for
X6/DI1 = LOW via C0468.
^ 69
7.
Connect mains voltage.
The detection of the mains voltage takes about 1 second. If
the mains voltage is within the operating range (
^ 103)
l
the green LED at the power supply module will be
blinking.
l
XT keypad displays "ok".
8.
Select operating mode.
C0001 = 0
Operation via system bus (CAN) with master
control
^ 64
C0001 = 1
Control via digital inputs
^ 65
C0001 = 2
Operation via EtherCAT with master control
l
For this purpose, use the EtherCAT module
EMF2192IB.
^ 66