2 connection to the dc bus (+ug, -ug), Connection to the dc bus (+ug, −ug), Electrical installation – Lenze ECSCExxx Power supply module User Manual
Page 45: Stop

Electrical installation
Power terminals
Connection to the DC bus (+U
G
, −U
G
)
l
45
EDBCSXE040 EN 7.0
5.3.2
Connection to the DC bus (+U
G
, −U
G
)
(
Stop!
ƒ
The supply of Lenze controllers of the 82xx and 93xx series is not permitted.
ƒ
If synchronous motors with a high centrifugal mass are used, a considerable
amount of energy can be fed back into the DC bus. Please take this into
account when dimensioning the brake resistor.
ƒ
If the total cable length is > 20 m, install an axis module or a capacitor module
directly at the power supply module.
ƒ
Design the ±U
G
cables twisted and as short as possible. Ensure short−circuit−proof
routing!
ƒ
Cable length (module
« module) > 30 cm: install shielded ±U
G
cables.
,
Documentation of the ECSxS/P/M/A axis modules
Observe the enclosed notes.
,
Documentation of the ECSxK capacitor module
Observe the enclosed notes.
Fuses
Fusing the DC−bus interconnection is not required if power supply modules of the ECS
series are used which are fused on the mains side.
Cable cross−section
Cable
length (modu
le/module)
Wire end ferrule
Cable cross−section Tightening torque
Stripping length
Up to 20 m
Without wire end
ferrule
6 mm
2
(AWG 10)
1.2 ... 1.5 Nm
(10.6 ... 13.3 lb−in)
5 mm for screw
connection
10 mm for spring
connection
With insulated wire end
ferrule
> 20 m
Without wire end
ferrule
10 mm
2
(AWG 8)
With insulated wire end
ferrule
Use pin−end connectors
for wiring!