Diagnostics
Advanced diagnostics via diagnostics PDO (CAN2_OUT)
l
113
EDBCSXE040 EN 7.0
10.2
Advanced diagnostics via diagnostics PDO (CAN2_OUT)
Via CAN2_OUT a diagnostics process data telegram (PDO) with display values concerning
the mains conditions and the internal state machine can be sent from the power supply
module. The diagnostics PDO consists of 8 bytes which can be assigned with variables.
ƒ
The 8 bytes of the PDO are assigned with variables via code C0390/1 ... 8.
ƒ
Depending on the byte size of the variables selected, it may happen that the
variables in the last subcodes do not become effective anymore.
ƒ
In C0391 the assignment in percent (0 ... 100 %) of the 8 bytes of the PDO is shown.
ƒ
For sending the diagnostics PDO the CAN bus has to be in the "Operational" state
and the cycle time for CAN2_OUT > 0 ms (C0356/2) has to be set.
Value
C0390/1 ... 8
Description
Size
0
Not assigned
0 bytes
1
Actual value of the input voltage V
L1L2 on the supply side
2 bytes
2
Actual value of the input voltage V
L2L3 on the supply side
2 bytes
3
Counter of the zero crossings per second (frequency measurement of V
L1L2
)
l
The zero crossings of the mains input voltage V
L1L2
are counted over the
interval of one second.
l
For a 50 Hz mains therefore 100 zero crossings result, for a 60 Hz mains 120
zero crossings.
l
If the characteristic of the variables is shown graphically, a saw−tooth profile
develops.
2 bytes
4
Mains synchronisation n−times outside the limits (evaluation of V
sd
and V
sq
)
l
For the evaluation of the mains input voltage the voltages L1, L2 and L3 are
transformed from alpha/beta to d/q and are scaled to the r.m.s. value of the
mains input voltage.
l
If the mains conditions are stable, the value of V
sd
will set to approx. 350,
and the value of V
sq
to approx. 0.
l
If the limit values of V
sd
or V
sq
are exceeded or too low, a counter is
incremented. If the limit values have been exceeded for the fourth time,
mains synchronism is no longer ensured and an LP1 error message is output.
l
Range for V
sd
: 300 ... 400
l
Range for V
sq
: −50 ... 50
1 byte 1
5
Internal status bits:
l
Bit 0 = 1: Mains voltage since switch−on (24 V) not OK.
l
Bit 1 = 1: An LP1 error was detected.
l
Bit 2: Switching status of the IGBT (0 = "chopping")
l
Bit 3 = 1: Saving of parameter set permitted.
l
Bit 4 = 1: A warning is active.
l
Bit 5 = 1: A message is active.
l
Bit 6 = 1: Calculation for mains synchronisation started.
l
Bit 7 = 1: Mains synchronisation is active.
1 byte 1
6
Value of the transformed voltage component V
sd
scaled to the r.m.s. value of
the mains input voltage. The value should be approx. 350.
2 bytes
7
Value of the transformed voltage component V
sq
scaled to the r.m.s. value of
the mains input voltage. The value should be approx. 0.
2 bytes