Appendix

Codes

12

l

132

EDBCSXE040 EN 7.0

Parameter

C0150

Designation

DCTRL status word 1

Data type: UNSIGNED_16

Index: 24425

dec

= 5F69

hex

Bit coded display of the internal status word 1

Display range

(min. value | unit | max. value)

0x0000

0xFFFF

Bits

(read only)

Information

Bit 0 Discharge DC bus (U

G

< 60 V)

Bit 1 Pulse inhibit (IMP)

Bit 2 I

max

limit current reached

Bit 3 Charging of the DC bus completed

Bit 4 Heatsink fan on/off

l

1 = the heatsink fan is switched on if the
temperature of the heatsink or the device interior
exceeds 50°C.

l

0 = the heatsink fan is switched off if the
temperature of the heatsink or the device interior
falls below 45°C.

Bit 5 I x t−warning active

Bit 6 I x t−limit reached

Bit 7 Controller inhibit (CINH)

Bit 8 Status code (binary, LSB)

Bit 9 Status code (binary)

Bit 10 Status code (binary)

Bit 11 Status code (binary, MSB)

Bit 12

Not assigned

...

Bit 15

Parameter

C0151

Designation

DCTRL status word 2 (high word)

Data type: UNSIGNED_16

Index: 24424

dec

= 5F68

hex

Bit coded display of the internal status word 2

Display range

(min. value | unit | max. value)

0x0000

0xFFFF

Bits

(read only)

Information

Bit 0

Not assigned

...

Bit 3

Bit 4 Fault/TRIP active

Bit 5 Short−circ. brake TRIP active

Bit 6 Not assigned

Bit 7 LP1 warning active

Bit 8 Power system ready (DC bus can be

charged)

Bit 9 No earth fault

Bit 10 Heatsink fan fault (FAN)

Bit 11 DC bus is charged externally

Bit 12

Not assigned

...

Bit 15