Configuring system bus (can) – Lenze ECSCExxx Power supply module User Manual
Page 91

Configuring system bus (CAN)
Setting the boot−up time/cycle time
l
91
EDBCSXE040 EN 7.0
Parameter
C0356
Name
CAN time settings
Data type: INTEGER_32
Index: 24219
dec
= 5E9B
hex
Setting of the ...
l
Boot−up time
l
Cycle time
l
Activation delay
^ 90
Setting range
(min. value | unit | max. value)
0
ms
65000
Subcodes
Lenze setting
Information
C0356/1
3000 ms
CAN boot−up time
l
Delay time after mains connection for the
initialisation by the master.
l
Only valid if C0352 = 1 (master).
C0356/2
0 ms
Cycle time for CAN2_OUT
l
Diagnostics PDO C0390 (
^ 98)
C0356/3
0 ms
Cycle time for CAN3_OUT
l
Factor to task time for process data telegram
transmission.
l
0 ms = event−controlled data transmission (the
output data will only be transmitted if a value
changes in the output object)
C0356/4
20 ms
Delay time for initial transmission of the process data
object CAN3_OUT after the CAN bus changes to
"Operational"
Save changes with C0003 = 1.
The settings are only accepted after carrying out one of the following actions:
ƒ
Renewed switch−on of the 24 V low−voltage supply
ƒ
Reset node via the bus system (by the network management (NMT))
ƒ
Reset node with C0358 = 1
)
Note!
If reset node is executed via GDC, communication will be interrupted. You
therefore have to log in again manually or find the devices connected to the
bus once again (fieldbus scan).