Electrical installation
Wiring of system bus (CAN)
l
58
EDBCSXE040 EN 7.0
Bus cable length
)
Note!
The permissible cable lengths must be observed.
1. Check the compliance with the total cable length in Tab. 5−1.
The baud rate determines the total cable length.
CAN baud rate [kbit/s]
Max. bus length [m]
50
1500
125
630
250
290
500
120
1000
25
Tab. 5−1
Total cable length
2. Check the compliance with the segment cable length in Tab. 5−2.
The segment cable length is determined by the cable cross−section used and the number
of nodes. Without a repeater, the segment cable length corresponds to the total cable
length.
Number of nodes
Cable cross−section
0.25 mm
2
0.5 mm
2
0.75 mm
2
1.0 mm
2
2
240 m
430 m
650 m
940 m
5
230 m
420 m
640 m
920 m
10
230 m
410 m
620 m
900 m
20
210 m
390 m
580 m
850 m
32
200 m
360 m
550 m
800 m
63
170 m
310 m
470 m
690 m
Tab. 5−2
Segment cable length
3. Compare the two values detected.
If the value detected from Tab. 5−2 is smaller than the total cable length to be provided
from Tab. 5−1 , repeaters must be used. Repeaters divide the total cable length into
segments.
Example: Selection help
Specifications
l
Cable cross−section:
0.5 mm
2
(according to cable specifications
^ 57)
l
Number of nodes:
63
l
Repeater:
Lenze−repeater, type 2176 (cable reduction: 30 m)
For the max. number of nodes (63), the following cable lengths / number of repeaters from
the specifications must be observed:
Baud rate [kbit/s]
50
120
250
500
1000
Max. cable length [m]
1500
630
290
120
25
Segment cable length [m]
310
310
290
120
25
Number of repeaters
5
2
−
−
−