Configuring system bus (CAN)
Setting the CAN node address and baud rate
Settings via codes
l
84
EDBCSXE040 EN 7.0
8.1.2
Settings via codes
)
Note!
ƒ
The settings in C0350 (CAN node address) and C0351 (baud rate) are only
used if the (address) switches 2 ... 7 of the DIP switch S1 are switched off
(OFF).
ƒ
If only one (address) switch 2 ... 7 is switched on (ON), the settings of the DIP
switch S1 usually apply.
ƒ
The baud rate (C0351) must be set identically for all CAN bus nodes.
ƒ
If the Lenze setting has been loaded via C0002,
– C0351 is set to 0 (500 kbit/s);
– you have to reset the baud rate (C0351) and the CAN node address
(C0350).
Parameter
C0350
Designation
CAN node address
Data type: INTEGER_32
Index: 24225
dec
= 5EA1
hex
Setting of the CAN node address
Note:
l
This code is not active if one of the switches 2 ... 7 of the DIP switch is set to "ON". (
^ 82)
l
After the setting, a reset node is required.
l
Each CAN node must be assigned a definite node address.
Setting range
(min. value | unit | max. value)
Lenze setting
1
63 32
Parameter
C0351
Designation
CAN baud rate
Data type: INTEGER_32
Index: 24224
dec
= 5EA0
hex
Entry of the CAN baud rate
Note:
l
The baud rate must be set identically for all CAN nodes.
l
This code is not active if one of the switches 2 ... 7 of the DIP switch is set to "ON". (
^ 82)
l
After the setting, a reset node is required.
Selection list
(Lenze setting printed in bold)
Information
0 500 kbps
1 250 kbps
2 125 kbps
3 50 kbps
4 1000 kbps