Electrical installation – Lenze ECSCExxx Power supply module User Manual
Page 57

Electrical installation
Wiring of system bus (CAN)
l
57
EDBCSXE040 EN 7.0
Assignment of the plug connectors
X4 (CAN)
X14 (CAN−AUX)
Description
CH
CAH
CAN−HIGH
CL
CAL
CAN−LOW
CG
CAG
Reference potential
Specification of the transmission cable
We recommend the use of CAN cables in accordance with ISO 11898−2:
CAN cable in accordance with ISO 11898−2
Cable type
Paired with shielding
Impedance
120
W (95 ... 140 W)
Cable resistance/cross−section
Cable length
£ 300 m £ 70 mW/m / 0.25 0.34 mm
2
(AWG22)
Cable length 301 1000 m
£ 40 mW/m / 0.5 mm
2
(AWG20)
Signal propagation delay
£ 5 ns/m
This manual is related to the following products: