Electrical installation – Lenze ECSCExxx Power supply module User Manual
Page 59

Electrical installation
Wiring of system bus (CAN)
l
59
EDBCSXE040 EN 7.0
Check repeater application
Given:
l
Baud rate:
125 kbps
l
Cable cross−section:
0.5 mm
2
l
Number of nodes:
28
l
Cable length:
450 m
Procedure
Cable length
See
1. Total cable length at 125 kbps:
630 m
2. Segment cable length for 28 bus nodes and a cable cross−section of
0.5 mm
2
:
360 m
3. Comparison: The value under point 2 is smaller than the required cable length of 450 m.
Conclusion
l
It is not possible to use a cable length of 450 m without using a repeater.
l
After 360 m (point 2) a repeater must be installed.
Result
l
The Lenze repeater type 2176 is used (cable reduction: 30 m)
l
Calculation of the maximum cable length:
First segment: 360 m
Second segment: 360 m (according to Tab. 5−1) minus 30 m (cable reduction when a repeater is used)
à
Maximum possible cable length with repeater: 690 m.
à
Now it is possible to use the required cable length.
)
Note!
Repeaters are recommended as a
ƒ
Service interface
Advantage: Trouble−free connecting during bus operation is possible.
ƒ
Calibration interface
Advantage: Calibration/programming unit remains electrically isolated.