1 fault responses, Fault responses, Monitoring functions – Lenze ECSCExxx Power supply module User Manual
Page 100

Monitoring functions
Fault responses
l
100
EDBCSXE040 EN 7.0
9.1
Fault responses
Reaction
ð Consequence
Display
Keypad XT
RDY
IMP
Fail
TRIP / Short−circuit
braking TRIP
o
n
n
TRIP active:
ð The charging of the DC bus is stopped. With short−circuit braking
TRIP the DC bus is quickly discharged via the brake resistor.
ð The drive is coasting (no control).
ð The system bus (CAN) indicates to the master that the power
supply module is not ready for operation.
TRIP is reset:
ð The power supply module is ready for operation again.
ð The charging of the DC bus is continued.
Message
Danger!
The drive restarts automatically if the message is removed.
o
n
n
Message active:
ð The charging of the DC bus is stopped.
ð The drive is coasting (no control).
ð The system bus (CAN) indicates to the master that the power
supply module is not ready for operation.
Message is reset:
ð The power supply module is ready for operation again.
ð The charging of the DC bus is continued.
Warning
ð The failure is only displayed, the drive continues to run normally.
n
o
n
Off
STOP!
The drive can be destroyed due to deactivated monitoring
functions.
˘
˘
˘
ð There is no response to the failure.
o = off
n = on
Responses (
¶ 100) of monitoring functions can be parameterised partly via codes ˘ in the
GDC parameter menu under Monitoring.