Diagnostics

Diagnostics with PCAN−View

Monitoring of telegram traffic on the CAN bus

10

l

117

EDBCSXE040 EN 7.0

The "Receive" and "Transmit" windows now continuously display the CAN telegrams.

On the basis of the IDs displayed, you can assign the telegrams to the devices.

If no telegrams are displayed, this may be caused by various factors:

ƒ

Is your Engineering PC connected to the correct CAN bus?

ƒ

Is the correct system bus adapter activated under "System control, CAN Hardware"?

ƒ

What does the status line of the »PCAN−View« contain?
In case of "Bus Heavy" mostly a node with a wrong baud rate disturbs the bus traffic.

ƒ

Do the devices are in the "Operational" status?