Troubleshooting and fault elimination – Lenze ECSCExxx Power supply module User Manual
Page 124

Troubleshooting and fault elimination
Fault messages
Causes and remedies
l
124
EDBCSXE040 EN 7.0
Remedy
Cause
Description
Fault message
Remedy
Cause
Description
Display
No.
0070 U15
Undervoltage of external
low−voltage supply
Voltage
< 17 V
Check low−voltage supply
0071 CCr
System failure
Strong interference on control
cables
Control cables must be shielded
Ground or earth loops in wiring
PE wiring
0072 PR1
Checksum error in parameter
set 1
Contact Lenze
0079 PR5
Internal fault (EEPROM)
Contact Lenze
0095 FAN1
Fan monitoring (only for built−in
units ECSEE)
Heatsink fan
l
blocked
l
dirty
l
defective
Eliminate cause
0105 H05
Internal fault (memory)
Contact Lenze
0106 H06
Internal fault (power section)
During initialisation of the
power supply module a wrong
power stage has been detected
Contact Lenze
0260
1260
2260
NodeGuard Trp
NodeGuard Msg
NodeGuard Wrn
"Life Guarding Event"
The power supply module as
CAN slave does not receive a
node guarding telegram from
the CAN master within the
"Node Life Time".
l
Check wiring at X4.
l
Check CAN configuration
l
Make sure that "Node
Guarding" has been activated
in the CAN master.
l
Adapt "Node Life Time"
(C0382, C0383) to the setting
in the CAN master.