Technical data, General data and operating conditions – Lenze ECSCExxx Power supply module User Manual
Page 21

Technical data
General data and operating conditions
l
21
EDBCSXE040 EN 7.0
General electrical data
EMC
Compliance with the requirements acc. to EN 61800−3
Noise emission
Compliance with the limit class C2 according to EN 61800−3(achieved with a
collective filter typical for the application)
Noise immunity
Requirements acc. to EN 61800−3
Requirement
Standard
Severity
ESD
1)
EN 61000−4−2
3, i. e.
l
8 kV for air discharge
l
6 kV for contact discharge
Conducted high frequency
EN 61000−4−6
10 V; 0.15 ... 80 MHz
RF interference (housing)
EN 61000−4−3
3, i. e. 10 V/m;
80 ... 1000 MHz
Burst
EN 61000−4−4
3/4, i. e. 2 kV/5 kHz
Surge (surge voltage on
mains cable)
EN 61000−4−5
3, i. e. 1.2/50
ms
l
1 kV phase/phase
l
2 kV phase/PE
Insulation resistance
EN 61800−5−1, UL 840: Overvoltage category III
Discharge current to PE
(Acc. to EN 61800−5−1)
> 3.5 mA AC
Enclosure
IP20 for
l
Standard installation (built−in unit)
l
Cold−plate technique
l
Mounting with thermal separation (push−through technique), IP54 on heatsink
side
Protective measures against
l
Short circuit in power terminals (short−circuit−proof at mains connection)
l
Short circuit in auxiliary circuits
– Digital outputs: Short−circuit−proof
– Bus and encoder systems: Limited protection against short circuit (if
necessary, monitoring functions can be switched off, in this case, error
messages must be reset:)
l
Earth fault (earth−fault protected at mains connection)
l
Overvoltage
Protective insulation of control circuits
Protective separation from the mains
Double/reinforced insulation acc. to EN 61800−5−1
1)
The noise immunity with the severities given must be ensured by the control cabinet. The user must check the
compliance of the severities given.