2 drive system on the mains, 1 electrical isolation, Drive system on the mains – Lenze ECSCExxx Power supply module User Manual
Page 38: Electrical isolation, Electrical installation

Electrical installation
Drive system on the mains
Electrical isolation
l
38
EDBCSXE040 EN 7.0
5.2
Drive system on the mains
This information applies to the ECS drive system, consisting of:
ƒ
ECSxE... power supply module
ƒ
ECSxK series capacitor module (optional)
ƒ
ECSxS/P/M/A series axis module
ƒ
Motor
ƒ
Accessories
ƒ
Wiring
5.2.1
Electrical isolation
The integrated electrical isolation between the power section and the control section is a
protective separation (reinforced insulation) acc. to EN 61800−5−1.
To maintain this protective separation, it must be ensured that the external 24 V supply
and all components connected to this supply also have a protective separation (SELV/PELV)
acc. to EN 61800−5−1.
24 V supply
DC bus
X6/+24, GND
X22
Basic insulation (50 V)
Dig. input/output
X6/DI1, DI2, D24, DO1
Reinforced insulation
(300 V)
Thermostat
X6/T1, T2
CAN
X4
Mains
AIF
X21
X1
Fig. 5−1
Electrical isolation