beautypg.com

3 writing codes with two decimal positions, 12 implemented devicenet objects – Lenze E94AYCDN User Manual

Page 81

background image

Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17

81

12

Implemented DeviceNet objects

12.11

Examples for reading/writing with the »Class Instance Editor«

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.11.3

Writing codes with two decimal positions

The current controller reset time is to be set to 6.50 ms using code C00076.
Enter the following in the input fields of the »Class Instance Editor« (fig.

[12-3]

):

• Description: Set Single Attribute (write code)
• Class: 6E (access to Lenze code)
• Instance: 4C (hex value of the code)
• Attribute: 1 (hex value of the subcode)
• ”Data sent to the device”: 28A = 650  "6.50" is written.
• Transmit data size: Double (4 bytes)

[12-3] »Class Instance Editor«: Writing codes with two decimal positions