C13863 | baud rate, C13864 | active mac id, C13880 | response in the case of comm. fault – Lenze E94AYCDN User Manual

Page 54: C13864, C13863, C13880/1, C13880/2, C13880/3, 11 parameter reference

background image

11

Parameter reference

11.2

Parameters of the communication module for the MXI1 slot

54

Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13863

C13864

C13880

Parameter | Name:

C13863 | Baud rate

Data type: UNSIGNED_8

Index: 10712 = 0x29D8

Display of the baud rate
Selection list

(read only)

0 125.00 kbps
1 250.00 kbps
2 500.00 kbps

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13864 | Active MAC ID

Data type: UNSIGNED_8

Index: 10711 = 0x29D7

Display of the active MAC ID
Display area

(min. value | unit | max. value)

0

255

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13880 | Response in the case of comm. fault

Data type: UNSIGNED_8

Index: 10695 = 0x29C7

Monitoring response in the case of communication fault

A change in the monitoring response becomes immediately effective.
Selection list

0 No Response
1 Fault
3 Quick stop by trouble
4 Warning Locked
6 Information

Subcodes

Lenze setting

Info

C13880/1

0: No Response

Idle Mode

C13880/2

0: No Response

Timeout I/O connection

C13880/3

0: No Response

Communication error

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT