beautypg.com

5 voltage supply, Voltage supply, Voltage supply ( 29) – Lenze E94AYCDN User Manual

Page 29: 5installation

background image

Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17

29

5

Installation

5.2

Electrical installation

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.2.5

Voltage supply

The communication module is externally supplied with voltage at the 5-pole plug connector (X225)

via the DeviceNet line.

• The communication module always requires an external voltage supply.
• Communication with a standard device that is separated from the mains is not possible.

Terminal data (X225)

Note!

Use a safely separated power supply unit (SELV/PELV) in accordance with EN 61800-5-1.

Terminal

Cable colour

Description

V+

red

External voltage supply

• U = 24 V DC

• I

max

= 170 mA

V-

Black

Reference potential for external voltage supply

Area

Values

Electrical connection

Plug connector with double screw connection

Possible connections

rigid:

2.5 mm

2

(AWG 14)

flexible:

without wire end ferrule

2.5 mm

2

(AWG 14)

with wire end ferrule, without plastic sleeve

2.5 mm

2

(AWG 14)

with wire end ferrule, with plastic sleeve

2.5 mm

2

(AWG 14)

Tightening torque

0.5 ... 0.6 Nm (4.4 ... 5.3 lb-in)

Bare end

7 mm