4 technical data, 1 general data and operating conditions, Technical data – Lenze E94AYCDN User Manual
Page 15: General data and operating conditions, 4technical data
Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17
15
4
Technical data
4.1
General data and operating conditions
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4
Technical data
4.1
General data and operating conditions
Area
Values
Order designation
E94AYCDN
Communication profile
DeviceNet
Interface
5-pole plug connector with screw connection
Communication medium
EN 11898
Network topology
Line terminated at both ends (R = 120 )
Number of nodes
Max. 64
Max. cable length
500 m (dependent on the selected baud rate and the cable type used)
DeviceNet nodes
Slave
Vendor ID
445 (0x1BD)
Device type
0 (generic device)
Product code
9400 (0x24B8)
Baud rate
125, 250, 500 kbps (adjustable via DIP switch)
Voltage supply
External supply via the 5-pole plug connector
V+ : U = 24 V DC, I
max
= 170 mA
V- : reference potential for external voltage supply
Conformities , approvals
• CE
• UL
(see also hardware manual)
Servo Drives 9400 hardware manual
Here you can find the ambient conditions and information on the electromagnetic