C14864 | active mac id, C14880 | response in the case of comm. fault, C14883 | data length of i/o data consumed – Lenze E94AYCDN User Manual
Page 61: C14883, C14864, C14880/1, C14880/2, C14880/3, 11 parameter reference
Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17
61
11
Parameter reference
11.3
Parameters of the communication module for the MXI2 slot
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14864
C14880
C14883
Parameter | Name:
C14864 | Active MAC ID
Data type: UNSIGNED_8
Index: 9711 = 0x25EF
Display of the active MAC ID
Display area
(min. value | unit | max. value)
0
255
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14880 | Response in the case of comm. fault
Data type: UNSIGNED_8
Index: 9695 = 0x25DF
Monitoring response in the case of communication fault
A change in the monitoring response becomes immediately effective.
Selection list
0 No Response
1 Fault
3 Quick stop by trouble
4 Warning Locked
6 Information
Subcodes
Lenze setting
Info
C14880/1
0: No Response
Idle Mode
C14880/2
0: No Response
Timeout I/O connection
C14880/3
0: No Response
Communication error
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14883 | Data length of I/O data consumed
Data type: UNSIGNED_8
Index: 9692 = 0x25DC
Setting of the data length (in bytes) of the I/O data received by the device via DeviceNet.
Note:
• If the data length is changed, the DeviceNet scanner will be informed about this change (consumed data size).
• If the data length is reduced, it must be checked before whether the intended data length is sufficient for the
application.
• If the data length of the consumed I/O data does not correspond to the length of the mapped ports which is
specified by the drive via PDO mapping, the
DeviceNet: Consumed I/O data length is contradictory [0x00C88211]
error message is generated and entered as a warning into the logbook of the standard device.
• If the number of consumed I/O data deviates from the Lenze setting (4 bytes), the "Automap on Add" function in
the scanner configuration dialog of the »RSNetWorx« software has to be deactivated and the number of the
process data words has to be adapted via the "Edit I/O parameters" button.
Setting range
(min. value | unit | max. value)
Lenze setting
0
64 4
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT