Devicenet: communication error [0x00c88121, Devicenet: online [0x00c88141, 0x00c88211] ( 46) – Lenze E94AYCDN User Manual
Page 46: And entered as a warning in, Devicenet: produced i/o data length is, Contradictory [0x00c88212] ( 46), Be generated and entered as a warning, 0x00c88121, 0x00c88141, 0x00c88211
10
Error messages
10.2
Possible causes and remedies
46
Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
DeviceNet: Communication error [0x00c88121]
DeviceNet: Online [0x00c88141]
DeviceNet: Consumed I/O data length is contradictory [0x00C88211]
DeviceNet: Produced I/O data length is contradictory [0x00C88212]
Response (Lenze setting printed in bold)
Setting:
/
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
A communication error occurred
Check cables and terminals.
Response (Lenze setting printed in bold)
Setting: not possible
None System error Error Fault Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The DeviceNet is online
-
Response (Lenze setting printed in bold)
Setting: not possible
None System error Error Fault Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The number of consumed I/O data via DeviceNet does
not correspond to the number configured by the
standard device through port mapping (displayed in
/
)
Check whether the differing data length is sufficient for
the application. If required, adapt the port mapping or
the data length of the I/O data consumed via
/
Response (Lenze setting printed in bold)
Setting: not possible
None System error Error Fault Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The number of produced I/O data via DeviceNet does not
correspond to the number configured by the standard
device through port mapping (displayed in
/
)
Check whether the differing data length is sufficient for
the application. If required, adapt the port mapping or
the data length of the I/O data produced via
/