beautypg.com

8 monitoring, 1 interruption of the devicenet communication, Monitoring – Lenze E94AYCDN User Manual

Page 39: Interruption of the devicenet communication, 8monitoring

background image

Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17

39

8

Monitoring

8.1

Interruption of the DeviceNet communication

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8

Monitoring

8.1

Interruption of the DeviceNet communication

An interruption of the DeviceNet communication, e.g. by a cable break or a failure of the host (PLC,

scanner), is detected by the communication module.
Responses to communication faults can be set in the DeviceNet object

Lenze Class (0x65 / 101)

( 74)

or under the Monitoring tab:

Settings

Description

Idle Mode

The scanner does not transmit any I/O data if it is in idle state.

If the device (communication module) is in the idle state, the response

parameterised here (

C13880/1

/

C14880/1

) is activated in the drive.

I/O connection timeout

The data transmission of the poll or CoS/Cyclic I/O connections can be

monitored by timeouts.

The timeout values are configured within the

Connection Class (0x05 / 5)

( 70)

- instance 2 (poll I/O) or instance 4 (CoS/Cyclic I/O), attribute 9.

After the monitoring time has elapsed, the response parameterised here

(

C13880/2

/

C14880/2

) is activated in the drive.

Communication error

The device (communication module) automatically recognises

communication faults.

If a communication fault is active, the response parameterised here

(

C13880/3

/

C14880/3

) is activated in the drive.