4 connection class (0x05 / 5), Connection class (0x05 / 5), Configured within the – Lenze E94AYCDN User Manual
Page 70: 12 implemented devicenet objects
12
Implemented DeviceNet objects
12.4
Connection Class (0x05 / 5)
70
Lenze · E94AYCDN communication module (DeviceNet™) · Communication Manual · DMS 5.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.4
Connection Class (0x05 / 5)
This object contains some information relating to connection settings:
• "Explicit Messages" (instance 1)
• "Poll I/O" (instance 2)
• "CoS/Cyclic I/O" (instance 4)
Instance 1 ("Explicit Messages" connection)
Attribute
Service(s)
Designation
Data type
Value
1
GET
state
USINT
Status of the object
0: Nonexistent
1: Configuring
2: Waiting for connection ID
3: Established
4: Timed Out
5: Deferred Delete
2
GET
instance_type
USINT
0 (Explicit Message)
3
GET
transportClass_trigger
BYTE
131 (0x83)
4
GET
produced_connection_id
UINT
Transmitting CAN identifier
5
GET
consumed_connection_id
UINT
Receiving CAN identifier
6
GET
initial_comm_characteristics BYTE
33 (0x21)
7
GET
produced_connection_size
UINT
132 (0x84)
Maximum amount of data
produced
8
GET
consumed_connection_size UINT
132 (0x84)
Maximum amount of data
consumed
9
1)
GET / SET
expected_packet_rate
UINT
Connection-dependent
Lenze setting: 2500 ms
(0x9C4)
10
-
Not in use
-
Not defined
11
-
Not in use
-
Not defined
12
1)
GET / SET
watchdog_timeout_action
USINT
Defines time-out treatment
•
1 = Auto Delete
(Lenze
setting)
• 3 = Deferred Delete
13
GET
produced_connection_path
_length
UINT
0
14
GET
produced_connection_path
EPATH
-
15
GET
consumed_connection_path
_length
UINT
0
16
GET
consumed_connection_path EPATH
-
17
GET
production_inhibit_time
UINT
0
1) The device commands "Load Lenze setting", "Save start parameters", and "Load start parameters" do not have an