8 fault messages and alarms – JUMO 709062 TYA 202 - Three-Phase Power Controller Operating Manual User Manual
Page 94

8 Fault messages and alarms
92
2012-12-31/00561073 [SCR power switch TYA202]
Limiting active
high temperature
Device temperature is higher than 105 °C.
Device is too hot, power is reduced!
(limited power due to excess temperature)
- Ensure adequate ventilation
- Reduce load current
- Use power controller with
higher maximum load current
Supply voltage is
too low
Supply voltage is not within specified toler-
ance range
v Chapter 10.1 "Voltage supply, load
Check nominal voltage of the de-
vice type
Supply voltage is
too high
Supply voltage is not within specified toler-
ance range
Chapter 10.1 "Voltage supply, load cur-
rent"
Check nominal voltage of the de-
vice type
Temporary
drop in supply
Dangerous temporary equal proportion for
transformer loads has been detected.
Ensure stable mains supply.
Master-slave
rotary field error
Counterclockwise rotary field has been de-
tected
Master-slave
incorrectly wired.
Wiring fault has been detected
Rotary field detection
failed
Rotary field detection not possible
- Check connection
- Eliminate line disturbances
Wire break
Current input
Input current for the set measuring range out-
side the valid range.
- Check wiring for wire breaks
and reverse polarity.
- Check upstream devices
(controllers)
Wire break
Voltage input
Input current for the set measuring range out-
side the valid range.
- Check wiring for wire breaks
and reverse polarity.
- Check upstream devices
(controllers)
Malfunction
Bus error
No connection to the Profibus master
Check wiring and master device
(PLC).
Master-slave
Error in comm.
Error in the data transfer between master and
slave
Check data connection of patch
cable
Data cable
faulty
Communication between master and slave
interrupted.
Check the patch cable and re-
place, if necessary
Synchronization
failed
Slave device switched off or communication
between master and slave interrupted
Check data connection of patch
cable or voltage supply
Fault message
Cause
Remedy