8 Fault messages and alarms

92

2012-12-31/00561073 [SCR power switch TYA202]

Limiting active
high temperature

Device temperature is higher than 105 °C.
Device is too hot, power is reduced!
(limited power due to excess temperature)

- Ensure adequate ventilation

- Reduce load current

- Use power controller with

higher maximum load current

Supply voltage is
too low

Supply voltage is not within specified toler-
ance range

v Chapter 10.1 "Voltage supply, load

current"

Check nominal voltage of the de-
vice type

v Chapter 1.3 "Order details"

Supply voltage is
too high

Supply voltage is not within specified toler-
ance range

Chapter 10.1 "Voltage supply, load cur-
rent"

Check nominal voltage of the de-
vice type

v Chapter 1.3 "Order details"

Temporary
drop in supply

Dangerous temporary equal proportion for
transformer loads has been detected.

v Chapter 5.1.5 "Monitoring"

Ensure stable mains supply.

Master-slave
rotary field error

Counterclockwise rotary field has been de-
tected

v Chapter 3.3.1 "Rotary cur-

rent economic circuit mas-
ter-slave for resistive loads
in star or delta connection
or transformer loads (resis-
tive-inductive)"

Master-slave
incorrectly wired.

Wiring fault has been detected

Rotary field detection
failed

Rotary field detection not possible

- Check connection

v Chapter 3.3 "Connection

diagram"

- Eliminate line disturbances

Wire break
Current input

Input current for the set measuring range out-
side the valid range.

- Check wiring for wire breaks

and reverse polarity.

- Check upstream devices

(controllers)

Wire break
Voltage input

Input current for the set measuring range out-
side the valid range.

- Check wiring for wire breaks

and reverse polarity.

- Check upstream devices

(controllers)

Malfunction
Bus error

No connection to the Profibus master

Check wiring and master device
(PLC).

Master-slave
Error in comm.

Error in the data transfer between master and
slave

Check data connection of patch
cable

Data cable
faulty

Communication between master and slave
interrupted.

Check the patch cable and re-
place, if necessary

Synchronization
failed

Slave device switched off or communication
between master and slave interrupted

Check data connection of patch
cable or voltage supply

Fault message

Cause

Remedy