9 What to do, if ...

What is happening?

Cause / remedy

Information

Green Power LED is
flashing

- Display switch-off active

h Press any key

v Chapter 5.1.1

"Device data"

Power controller is not
producing power
even though the green
Power LED
is lit and a setpoint value
has been set

- Parameters have been changed in the

configuration level but not completed

h Leave the configuration level by pressing

EXIT and wait for a restart

-

- Wire break at the analog input or incor-

rect analog input wiring

v Chapter 3.3

"Connection dia-
gram"

- Setpoint value configuration incorrectly

configured (e.g. set via interface).

v Chapter 5.1.4

"Setpoint value
configuration"

- Input for firing-pulse inhibit active

A padlock symbol is shown in the info line
as the operating mode

Undo connection between screw terminal 7
and 8 at terminal X2_2

v Chapter 4.1.2

"Displaying mea-
sured values"

- Load break

h Check load and load connections

v Chapter 8 "Fault

messages and
alarms"

Fuse LED is lit

- Semi-conductor fuse defective due to

short circuit in power section

h Remedy short circuit in the load or load

circuit

h Fit a new semi-conductor fuse

v Chapter 8.2 "Re-

placing a defec-
tive semi-conduc-
tor fuse"

Power controller is pro-
ducing power even
though no setpoint value
(output level) is specified
by the controller

- Configuration problem:

Controller output signal set to 4 to 20 mA
and analog input current on power con-
troller set to 0 to 20 mA.

h Check configuration and set same stan-

dard signals at the controller and power
controller

v Chapter 5.1.3

"Analog inputs"

v Chapter 5.1.4

"Setpoint value
configuration"

- Power controller in manual mode

h Exit manual mode by pressing EXIT

v Chapter 6.2

"Manual mode"

- Base load default value set

h Check settings for base load default val-

ue

v See "Base load"

on page 57

- SCR short circuit

v Chapter 8 "Fault

messages and
alarms"