8 Fault messages and alarms

Cyclical
display

The symbols for input, subordinate control, and operating mode are displayed
alternately in the info line together with fault messages or information about
particular statuses.

v Chapter 8 "Fault messages and alarms"

Examples

Fault message

Cause

Remedy

Limit value monit.
Min. value reached

The value has gone below the set limit value
for the min. alarm

-

Limit value monit.
Max. value reached

The set limit value for the max. alarm has
been exceeded

-

Fault at connected
load

Break or short-circuit of a load resistor.

v Chapter 6.1 "Detection of load

faults"

Replace defective heating ele-
ments.

Malfunction blown
fuse
(red LED fuse is lit)

1. Semi-conductor fuse defective

v Chapter 8.2 "Replacing a

defective semi-conductor
fuse"

2. No voltage at terminal U1

- Check wiring

- Check the line fuse for the

load circuit

3. The voltage supply for the control electron-
ics L1/N does not have the same phase angle
as the load circuit U1/U2.

Check wiring

4. SCR in the master power controller defec-
tive (only with three-phase economy circuit
where nominal voltage < 230 V)

The device must be returned to
JUMO for repair.

h Return the device

Malfunction
SCR breakage

SCR defective

The device must be returned to
JUMO for repair.

h Return the device

SCR short circuit

SCR defective
Note:
Monitoring only functions when the load re-
sistance is so low that at least 10 % of the
power controller nominal current is flowing.

The device must be returned to
JUMO for repair.

h Return the device

Caution!
High temperature

Device temperature is higher than 100 °C
(excess temperature)

- Ensure adequate ventilation

- Reduce load current

- Use power controller with

higher maximum load current