8 fault messages and alarms, Fault messages and alarms, Chapter 8 "fault messages and alarms – JUMO 709062 TYA 202 - Three-Phase Power Controller Operating Manual User Manual
Page 93

2012-12-31/00561073 [SCR power switch TYA202]
91
8 Fault messages and alarms
Cyclical
display
The symbols for input, subordinate control, and operating mode are displayed
alternately in the info line together with fault messages or information about
particular statuses.
v Chapter 8 "Fault messages and alarms"
Examples
Fault message
Cause
Remedy
Limit value monit.
Min. value reached
The value has gone below the set limit value
for the min. alarm
-
Limit value monit.
Max. value reached
The set limit value for the max. alarm has
been exceeded
-
Fault at connected
load
Break or short-circuit of a load resistor.
v Chapter 6.1 "Detection of load
Replace defective heating ele-
ments.
Malfunction blown
fuse
(red LED fuse is lit)
1. Semi-conductor fuse defective
2. No voltage at terminal U1
- Check wiring
- Check the line fuse for the
load circuit
3. The voltage supply for the control electron-
ics L1/N does not have the same phase angle
as the load circuit U1/U2.
Check wiring
4. SCR in the master power controller defec-
tive (only with three-phase economy circuit
where nominal voltage < 230 V)
The device must be returned to
JUMO for repair.
h Return the device
Malfunction
SCR breakage
SCR defective
The device must be returned to
JUMO for repair.
h Return the device
SCR short circuit
SCR defective
Note:
Monitoring only functions when the load re-
sistance is so low that at least 10 % of the
power controller nominal current is flowing.
The device must be returned to
JUMO for repair.
h Return the device
Caution!
High temperature
Device temperature is higher than 100 °C
(excess temperature)
- Ensure adequate ventilation
- Reduce load current
- Use power controller with
higher maximum load current