2012-12-31/00561073 [SCR power switch TYA202]

65

5 Configuration

5.2 Configuration example

Requirements

Load voltage on the power controller 400 V

Load voltage 230 V (for wye connection)

3 heating elements (each with 1 kW connected in parallel)

Load current: 9000 W / (3 x 230 V) = 13 A

Temperature coefficient TC = 1

Subordinate control loop: U

2

Base load: 0 %; maximum output level 100 %

Default setpoint value via standard signal of 0 to 20 mA

These requirements are sufficient for the following power controllers:

Device type

709062/X-01-020-100-400-252

Attention:
- Make sure that the rotating

electric field is right handed!

- Only possible in burst firing mode
- SCR load voltage =U

L

Fuse for contr

ol

electr

onics 2A

Fusing to pr

otect the

power section cabling

0(4)to 20mA

Setpoint lnput:

U

= phase-phase voltage

U

= phase-neutral voltage

U

= voltage on thyristor power unit

L

N

Thy

P

= total controlled power

I

= current in phase conductor

I

= current in thyristor power unit

tot

L

Thy

Ohmic load star
connection

U1

U2

N/L2

L1

V

13

14

15

12

11

10

89

7

6

5

4

2
3

1

8

1

U1

U2

Semiconductor-

fuse

Semiconductor-

fuse

N/L2

L1

V

13

14

15

12

11

10

89

7

6

5

4

2
3

1

8

1

S

Relay

Ö

P

-

+

Patchcable

TYA 202

E

Optocoupler

C

U

= U

Thy

L

I

=

Thy

P

tot

3 · U

N

=

P

tot

3 U

L

·

I

=

Thy

I

L

I

Thy

L1

N

L2 L3

PE

U

L

U

N

I

L