2 operator level, 1 device data, 2 power controller – JUMO 709062 TYA 202 - Three-Phase Power Controller Operating Manual User Manual

Page 46: Operator level, Device data, Power controller, 4 operation

background image

4 Operation

44

2012-12-31/00561073 [SCR power switch TYA202]

4.2 Operator level

Here you will find the parameters that can be modified during ongoing oper-
ation
without restarting (resetting) the device.
They can be accessed ex works without a password, but can also be protect-
ed with a 4-digit code, if necessary.

v Chapter 5.1.11 "Changing codes"

During ongoing operation, the power controller can be adapted to the plant
and optimized.

h In the measured value overview, press the

key

h Select the operator level and press

again.

Editing a pa-
rameter

The changes are effective immediately.
Once the correct setting (e.g. for display contrast) has been found, the param-

eter can be stored by pressing

.

If you do not want to apply the value, the entry can be aborted by pressing

.

4.2.1 Device data

4.2.2 Power controller

Value range

Description

0 to 50 to 100 %

50 % is set ex works.

0000 to 1440 min

0000 minutes are set ex works,
which means the display is not switched off.

k

/ bold = factory setting

Value range

Description

0 to 70 to 90 °el

70 °el are set ex works.

If "

α

start" is set to "No" in the configuration, this window is

not displayed and

α

start is set to 0 °el.