2 operator level, 1 device data, 2 power controller – JUMO 709062 TYA 202 - Three-Phase Power Controller Operating Manual User Manual
Page 46: Operator level, Device data, Power controller, 4 operation

4 Operation
44
2012-12-31/00561073 [SCR power switch TYA202]
4.2 Operator level
Here you will find the parameters that can be modified during ongoing oper-
ation without restarting (resetting) the device.
They can be accessed ex works without a password, but can also be protect-
ed with a 4-digit code, if necessary.
v Chapter 5.1.11 "Changing codes"
During ongoing operation, the power controller can be adapted to the plant
and optimized.
h In the measured value overview, press the
key
h Select the operator level and press
again.
Editing a pa-
rameter
The changes are effective immediately.
Once the correct setting (e.g. for display contrast) has been found, the param-
eter can be stored by pressing
.
If you do not want to apply the value, the entry can be aborted by pressing
.
4.2.1 Device data
4.2.2 Power controller
Value range
Description
0 to 50 to 100 %
50 % is set ex works.
0000 to 1440 min
0000 minutes are set ex works,
which means the display is not switched off.
k
/ bold = factory setting
Value range
Description
0 to 70 to 90 °el
70 °el are set ex works.
If "
α
start" is set to "No" in the configuration, this window is
not displayed and
α
start is set to 0 °el.