CHECK THERMOSTAT OPERATION. Raise and

lower thermostat setting as required to start and stop

burners.

19.

CHECK HIGH LIMIT CONTROL. Jumper

Thermostat terminals or thermostat connections in

Limit Control. Allow burners to operate until shutdown

by limit. REMOVE JUMPER.

20.

TEST IGNITION SYSTEM SAFETY SHUT-OFF

DEVICE AS FOLLOWS:

Place the boiler into operation by following the

appropriate lighting instructions in this manual.

Proceed with test as follows:
a. Thermocouple Pilot System
Using a 3/8” wrench loosen the thermocouple lead

at the gas valve. Main gas and pilot gas must shut

off. If not, replace gas valve.

b. EI Pilot System
Carefully remove ignitor sensor wire from ignition

module Main gas and pilot gas must shut off

immediately. If not, replace the module.

c. OP and EP Pilot Systems
Carefully remove the flame rod wire from terminal

“11” on the RM7890 Control. Main gas and pilot

gas must shut off. If not, replace the RM7890

Control.

21.

COMBUSTION CHAMBER BURN-OFF

a. The mineral wool combustion chamber panels

contain a cornstarch based binder that must be

burned out at installation to prevent odors during

subsequent boiler operation.

b. Ventilate the boiler room, set the high limit to its

maximum setting, set the thermostat to call for heat.

Allow the boiler to fire for at least an hour or until

the odor from the cornstarch has dissipated.

c. Return the high limit and thermostat to their desired

settings.

cAUTiON

Avoid operating this boiler in an environment

where saw dust, loose insulation fibers, dry wall

dust, etc. are present. If boiler is operated under

these conditions, the burner interior and ports

must be cleaned and inspected daily to insure

proper operation.