Table ii, Table iii – Burnham Series 5B User Manual
Page 31
31
FIG. 30
RECOMMENDED PIPING TO
BUILT-IN TANKLESS HEATERS
TABLe i - NATURAL GAS
Maximum Capacity of Piping in Cubic Feet of Gas Per Hour
(Based on a Pressure Drop of 0.3” Water
and 0.6 Specific Gravity)
Pipe
Length
in Feet
NOMINAL IRON PIPE SIZE IPS INCHES
¾
1
1¼
1½
2
2½
3
4
10
278
520
1050
1600
3050
4800
8500
17500
20
190
350
730
1100
2100
3300
5900
12000
30
152
285
590
890
1650
2700
4700
9700
40
130
245
500
760
1450
2300
4100
8300
50
115
215
440
670
1270
2000
3600
7400
60
105
195
400
610
1150
1850
3250
6800
70
96
180
370
560
1050
1700
3000
6200
80
90
170
350
530
990
1600
2800
5800
90
84
160
320
490
930
1500
2600
5400
100
79
150
305
460
870
1400
2500
5100
125
72
130
275
410
78
1250
2200
4500
150
64
12
250
380
710
1130
2000
4100
175
59
110
225
350
650
1050
1850
3800
200
55
100
210
320
610
980
1700
3500
TABLe ii
Multipliers to be used with Table I when Pressure Drop is not 0.3”
Pressure Drop
Multiplier
0.1
.577
0.2
.815
0.5
1.29
1.0
1.83
0.3
1.00
TABLe iii
Multipliers to be used with Tables I and II for
Specific Gravity Other than 0.60
Specific Gravity
Correction Factors
.50
1.10
.55
1.04
.60
1.00
.65
.96
.70
.93
36.
OPEN GAS TRAIN CARTON(S)
CONNECT GAS TRAIN(S) TO ELBOW ON END OF
MANIFOLD(S) according to the Gas Trains on pages
86, 87, 88, 89, 90, 91 or 92.
PRESSURE TESTING of gas service piping must be
done before connecting to the boiler gas train. Test for
leaks by introducing, from an isolated source, air or
inert gas to the piping. Piping shall withstand 3 PSI
gage pressure for a period of not less than 10 minutes
without showing any drop in pressure.
37.
A DRIP LEG SHOULD BE PROVIDED IN THE
VERTICAL DROP TO EACH GAS TRAIN, see
Fig. 1. An additional Manual Shut-off valve and
SecTiON iii – iNSTALLATiON iNSTRUcTiONS (continued)
must be mounted so that cut off point is above
marking on Lowest Permissible Water Line Plate.
f. Install Pressure Safety Relief Valve, using fittings
furnished, into 1-1/2” pipe tapping in upper corner
of End Section. DO NOT INSTALL A SHUTOFF
VALVE BETWEEN SAFETY RELIEF VALVE
AND BOILER. Safety Relief Valve must be
installed in a Vertical Position with handle up.
g. Install Boiler Drain Valve into one of unused return
tappings that has been bushed to ¾”. Drain Valve
can also be installed in return piping, preferably
in leg of tee that is located in line with return
connection on Boiler.
35.
CONNECT PIPING TO BUILT-IN HEATER(S) IF
USED, see Fig. 30, top - left side of this page.