failure on one OP Control System occur, the other OP

Control System would not be affected. Thus main

burners on the unaffected side would ignite on a “call

for heat” and would continue to operate until the

operating control was satisfied.

The OP Control System utilizes an RM7890C

microprocessor based integrated burner control and

a Q179D Rectification Pilot (standing or continuous

burning pilot) to which has been added to a Q309

Thermocouple. The RM7890C Primary Control is a

non-programming, amplifying relay which when used

with the Q179D Pilot provides solid state electronic

Flame Safeguard Protection during a “call for heat”

pilot failure. Main burners will shut down within 0.8

seconds and the RM7890C will lock out on safety

shutdown within 15 seconds. Should a pilot failure

occur during the “off” cycle, the thermocouple will cool

and within 45 to 90 seconds, will cause the L62GB-3C

Pilot Safety Switch to which it is connected, to break

the electrical circuit to the main gas valves as well as

shut off the flow of gas to the pilot. Thus 100% shut-

off is achieved.
a. LIGHTING INSTRUCTIONS

(1) Make sure all Manual Main Shut-off Valves and

all Pilot Valves have been off for at least five

minutes.

(2) Set Operating and Limit Controls to desired

settings.

(3) Turn on Main Electric Switch and Service

Switch.

(4) Open pilot valve on one side of boiler. Depress

button on L62GB-3C Pilot Safety Switch to

which it is connected and light pilot with match.

Continue to hold button in for one minute

or until pilot remains lighted after button is

released. Light pilot on opposite side of boiler

using same procedure.

(5) Press reset button on each RM7890C relay.
(6) Open Manual Main Shut-off Valves – main

burners will light.

Proceed to Paragraph 15

- Minimum Input

Adjustments (for diaphragm “Lo-Hi-Lo” or

motorized type gas valves)

SEQUENCE OF OPERATION OP – See Fig. 47
b. NORMAL OPERATION – 5015B thru 5026B

(1) When the operating control calls for heat,

terminal #6 of each RM7890C Burner Control is

energized.

(2) A component check circuit in each RM7890C is

activated which checks the electronic network of

the relay.

(3) Flame rod circuit between each Q179D pilot and

terminal “11” on its respective RM7890C proves

presence of flame electronically at its Q179D

pilot.

(4) Terminal #9 on each RM7890C is energized

supplying power to its respective main gas

valves.

(5) Main gas valves open and main burners are

ignited by the pilot flames.

(6) When operating control is satisfied, terminals

#6 and #9 on the RM7890C relays are de-

energized, main gas valves close and main

burners are extinguished.

(7) The Q179D pilots continue to burn.

c. SAFETY SHUTDOWN

(1) SAFETY SWITCH CIRCUIT

If limit control, Low Water Cut-off or any

other electrical safety switch opens, power

to terminal #6 and all other terminals on both

RM7890C relays are interrupted. Main Gas

Valves are thus de-energized and main gas

burners are immediately extinguished. Standing

pilot flames in the Q179D pilots will continue to

burn.

(2) PILOT FAILURE

(a) Flame rod supervision of the Q179D pilots

occur only during the operating cycle (call

for heat) since it is during this period that

the control is energizing the RM7890C

relays. If pilot failure occurs during this

period on one of the Q179D pilots, the main

gas valves controlled by that particular

RM7890C will close in 0.8 seconds. The

RM7890C will lockout on safety within 15

seconds. The burners controlled by the other

RM7890C will continue to burn.

(b) If pilot failure occurs on one of the Q179D

pilots during the “off” cycle of the operating

control, there will be no electronic flame rod

supervision since neither RM7890C relay

is energized during the “off” cycle. This is

due to utilization of a thermocouple in each

Q179D modified pilot which controls its

own pilot safety switch. This thermocouple

will cool in 45 to 90 seconds de-energizing

the pilot safety switch, which interrupts

the circuit between terminal #9 and the gas

valves and also shuts off the flow of gas to

the pilot. Thus 100% shut-off is achieved.

If the operating control calls for heat

during this period, the RM7890C relay will

immediately sense “no flame” on the pilot

SecTiON iV - OPeRATiON (continued)